Factors to Consider When Selecting an Inverter: Environmental Aspects

When selecting an inverter, environmental factors directly determine its operational stability, service life, and safety. Neglecting these factors may lead to frequent failures (such as overheating, short circuits, and corrosion) or even equipment damage. The following 6 core environmental factors require focused attention, and some factors need quantitative evaluation based on specific application scenarios:
Factors to Consider When Selecting an Inverter: Environmental Aspects

1. Temperature: A Core Factor Affecting Heat Dissipation and Component Life

Temperature is one of the most sensitive environmental factors for inverters. Internal components such as power modules (e.g., IGBTs) and capacitors are highly sensitive to temperature changes. Exceeding the allowable temperature range will directly shorten the service life or trigger protective shutdowns.

 

  • Operating Temperature Range:
    • The recommended operating temperature for conventional inverters is -10°C to 40°C (some industrial-grade models can extend this range to -20°C to 50°C). Priority should be given to models that match the on-site temperature.
    • If the on-site temperature exceeds 40°C, the inverter’s service life will shorten by approximately 2% to 3% for every 1°C increase. When the temperature is below 0°C, the fluidity of capacitor electrolyte decreases, which may cause startup failures. In such cases, models with “low-temperature startup protection” or “preheating function” should be selected.
  • Installation Requirements:
    • Avoid installing the inverter near heat sources (e.g., boilers, ovens, high-power motors). If avoidance is impossible, reserve a heat dissipation distance of at least 30 cm and add forced ventilation (e.g., installing cooling fans).
    • For outdoor or high-temperature environments (e.g., metallurgical plants, coking plants), select “high-temperature protective inverters” or equip them with thermal insulation and sunshades (to prevent sudden temperature rises in the cabinet due to direct sunlight).

2. Humidity: Preventing Insulation Breakdown and Short Circuits

Excessively high humidity can cause moisture absorption in the inverter’s internal circuit boards, reduce insulation performance, and even lead to short circuits in high-voltage parts (e.g., DC bus). Conversely, excessively low humidity may generate static electricity, interfering with control signals.

 

  • Humidity Range Requirements:
    • The recommended relative humidity is 40% to 60%, and the maximum allowable humidity should not exceed 90% (without condensation). Condensation is a key taboo, as it directly causes component rust and short circuits.
  • Countermeasures:
    • For high-humidity scenarios (e.g., textile mills, food processing workshops, basements): Select models with “moisture-proof coated” circuit boards, or install dehumidifiers (e.g., semiconductor dehumidifiers) or heaters (to prevent condensation in low-temperature and high-humidity conditions) inside the inverter cabinet.
    • For low-humidity scenarios (e.g., dry workshops, northern Chinese workshops with heating in winter): Ensure proper equipment grounding to avoid static accumulation interfering with the control circuit.

3. Dust and Corrosive Gases: Avoiding Blockages and Component Corrosion

Dust, oil stains, metal debris, or corrosive gases can block the inverter’s heat dissipation channels, corrode circuit boards and terminal blocks, and are among the main causes of inverter failures in industrial sites (e.g., mines, chemical plants, cement plants).

 

  • Dust/Foreign Object Protection:
    • Select the corresponding Ingress Protection (IP) rating based on the on-site dust concentration:
      • Ordinary workshops (with minimal dust): IP20 to IP30 (must be installed with a control cabinet to prevent large foreign objects from entering).
      • High-dust scenarios (e.g., flour mills, mines): IP54 to IP65 (dust-proof models, suitable for direct installation in outdoor or dusty environments).
      • Oil-stained scenarios (e.g., machine tool workshops, automobile manufacturing plants): Select models with “oil-proof coatings” to prevent oil accumulation from affecting heat dissipation.
  • Corrosive Gas Protection:
    • For chemical, electroplating, and printing and dyeing scenarios (containing acid, alkali, or salt spray gases): Prioritize “corrosion-resistant inverters” (with internal components and circuit boards treated for corrosion resistance), or isolate the environment using a sealed control cabinet with positive pressure ventilation (injecting clean air to prevent corrosive gases from entering).

4. Vibration and Shock: Preventing Mechanical Loosening and Component Damage

Inverters contain components susceptible to vibration, such as capacitors, terminal blocks, and cooling fans. Long-term vibration may cause loose wiring, component detachment, or even trigger fault protection.

 

  • Vibration Level Requirements:
    • Conventional inverters allow a vibration acceleration of 0.5g to 1g (g = gravitational acceleration, approximately 9.8 m/s²) within a vibration frequency range of 10 to 50 Hz.
    • For special scenarios (e.g., machine tools, vibrating screens, ships), select “vibration-resistant inverters” with reinforced internal component designs (e.g., soldered terminals, shockproof capacitors); some models can withstand vibration accelerations above 1.5g.
  • Installation Precautions:
    • Avoid installing the inverter on a rack directly connected to vibration sources (e.g., motors, pumps). Use shock-absorbing pads (e.g., rubber shock-absorbing pads) or independent brackets to isolate vibration.
    • Ensure secure fixation during vertical installation to prevent terminal blocks from bearing stress due to cabinet shaking.

5. Altitude: Affecting Heat Dissipation and Insulation Performance

Increasing altitude reduces air density, impairing heat dissipation efficiency (weaker air heat dissipation capacity). Additionally, air insulation strength decreases, increasing the risk of discharge in high-voltage parts.

 

  • Altitude Requirements:
    • The rated altitude for conventional inverters is below 1000 meters, where both heat dissipation and insulation performance meet design requirements.
    • For altitudes exceeding 1000 meters, measures such as “derated operation” or “enhanced heat dissipation” are necessary:
      • For every 1000-meter increase in altitude, the inverter’s rated output current should be reduced by 5% to 10% (to prevent overheating of power modules).
      • For high-altitude areas (e.g., plateaus, mountainous regions), select “plateau-type inverters” with higher-speed cooling fans, larger heat sink areas, and increased insulation spacing in high-voltage parts to prevent discharge.

6. Power Supply Environment: Avoiding Voltage Fluctuations and Harmonic Interference

The inverter’s input side relies on grid power supply. Grid issues such as voltage fluctuations, harmonics, and surges can damage the inverter’s rectifier module, trigger alarms (e.g., “undervoltage,” “overvoltage”), or even affect the operational accuracy of the motor on the output side.

 

  • Voltage Fluctuation Range:
    • Conventional inverters allow a grid voltage fluctuation of ±10% of the rated voltage (e.g., a 380V model can adapt to 342V to 418V).
    • For scenarios with large voltage fluctuations (e.g., rural power grids, heavy industry plants): Equip the system with input reactors or voltage stabilizers to suppress the impact of sudden voltage changes on the inverter.
  • Harmonic and Surge Protection:
    • For grids with high harmonics (e.g., simultaneous operation of multiple inverters and rectifier equipment): Install passive filters or active filters on the inverter’s input side to reduce harmonic interference with the inverter’s control circuit.
    • For thunderstorm-prone areas: Install surge protectors (SPDs) at the inverter’s power supply terminal to prevent damage to the rectifier module caused by high-voltage surges from lightning strikes.

Summary: Matching Table for Environmental Factors and Inverter Selection

Environmental Factor Key Specification Requirements Typical Application Scenarios Selection Recommendations
Temperature -10°C to 40°C (conventional), no high heat sources Ordinary workshops, office buildings Conventional model + natural heat dissipation
Temperature >40°C or < -10°C Metallurgical plants, cold storage High-temperature/low-temperature model + forced heat dissipation/preheating function
Humidity >60% (no condensation) or high humidity Textile mills, basements Moisture-proof model + dehumidifier
Dust/Oil Stains High dust or heavy oil contamination Mines, machine tool workshops IP54 + oil-proof coating + regular cleaning
Corrosive Gases Presence of acid, alkali, or salt spray Chemical plants, electroplating plants Corrosion-resistant model + positive pressure ventilation cabinet
Vibration Vibration acceleration > 0.5g Machine tools, ships Vibration-resistant model + shock-absorbing pads
Altitude > 1000 meters Plateaus, mountainous regions Plateau-type model or derated operation + enhanced heat dissipation
Power Fluctuations Voltage fluctuation > ±10% or high harmonics Rural power grids, heavy industry Input reactor + filter

 

In conclusion, inverter selection requires first conducting a “quantitative evaluation” of the on-site environment (e.g., measuring temperature, humidity, and altitude; identifying dust/gas types), then matching the protective rating, heat dissipation design, and anti-interference functions accordingly. This avoids increased later operation and maintenance costs or premature equipment damage due to “environmental mismatch.”