I. Core Basis for Inverter Brake Resistor Selection
The core function of an inverter brake resistor is to dissipate the regenerative energy of a motor. When the motor is in a deceleration, braking, or heavy-load lowering state (e.g., elevator descent, machine tool emergency stop), it acts as a generator and feeds energy back to the inverter’s DC bus. If this energy is not dissipated promptly, the bus voltage will rise excessively and trigger protection mechanisms. Selection should focus on “how to safely and efficiently dissipate regenerative energy,” with three core criteria: regenerative power, braking time, and allowable temperature rise.

II. Key Parameters to Confirm Before Selection (Prerequisites)
Before selecting a brake resistor, the following four types of basic parameters must be obtained, as they directly determine the resistor’s specifications:
- Rated Parameters of the Inverter and Motor
-
- Motor rated power \( P_{e} \) (kW, e.g., 5.5kW);
-
- Motor rated voltage \( U_{e} \) (V, e.g., 380V);
-
- Motor rated current \( I_{e} \) (A, can be estimated using \( P_{e} = \sqrt{3}U_{e}I_{e}\cos\varphi \), where \( \cos\varphi \) is 0.8~0.9);
-
- Inverter rated capacity \( S_{e} \) (kVA, usually matching the motor power—e.g., a 5.5kW motor typically requires an inverter with a capacity of approximately 7.5kVA).
- System Braking Requirements
-
- Braking type: Short-term braking (e.g., a single emergency stop of a machine tool) or continuous braking (e.g., frequent elevator up/down movements, crane load lowering);
-
- Braking time \( t_{b} \) (seconds, the time to decelerate from rated speed to a stop, e.g., 2s);
-
- Braking frequency: The number of braking cycles per unit time (e.g., 20 times per hour).
- Parameters of the Inverter’s Built-in Brake Unit
-
- If the inverter has a built-in brake unit (standard for most medium-to-high power inverters), check the manual to obtain the brake unit’s maximum allowable braking current \( I_{bmax} \) (A, e.g., 20A) and maximum allowable braking power \( P_{bmax} \) (kW, e.g., 15kW);
-
- If the inverter has no built-in brake unit, an external brake unit must be selected separately, and the matching between the brake unit and resistor should be considered simultaneously.
- Environmental Conditions
-
- Ambient temperature \( T_{amb} \) (℃, e.g., the normal workshop temperature of 25℃; a resistor with higher temperature resistance is required for high-temperature environments);
-
- Installation method: Natural cooling (no fan required) or forced air cooling (a fan is required, suitable for high-power scenarios).
III. Calculation of Core Brake Resistor Parameters (Key Steps)
The essence of brake resistor selection is to calculate two core specifications: resistance value \( R_{b} \) and resistor power \( P_{b} \). The specific calculation methods are as follows:
1. Calculate the Minimum Allowable Brake Resistance \( R_{bmin} \) (Avoid Current Overload)
The resistance value of the brake resistor cannot be too small; otherwise, the braking current will exceed the maximum allowable value of the inverter’s brake unit, burning the brake unit or resistor. The calculation formula is:\( R_{bmin} = \frac{U_{dc}}{I_{bmax}} \)
- \( U_{dc} \): The rated DC bus voltage of the inverter (V), which varies by input voltage type:
-
- Three-phase 380V input: \( U_{dc} \approx 1.35 \times 380 \approx 513V \) (approximately 540V at no load; 513V is used for calculation for safety at full load);
-
- Single-phase 220V input: \( U_{dc} \approx 1.35 \times 220 \approx 297V \);
- \( I_{bmax} \): The maximum allowable braking current of the inverter’s brake unit (A, obtained from the inverter manual, e.g., 18A).
Example: For a three-phase 380V inverter with a maximum allowable brake unit current of 20A:\( R_{bmin} = \frac{513}{20} \approx 25.65\Omega \)
→ The selected resistor value must be ≥25.65Ω (standard values such as 27Ω or 30Ω are usually chosen).
2. Calculate the Required Brake Resistor Power \( P_{b} \) (Avoid Burnout Due to Insufficient Power)
The resistor power must meet the requirement of “not exceeding the allowable temperature rise during braking.” Calculation methods differ for short-term braking and continuous braking scenarios:
(1) Short-Term Braking Scenario (Most Common, e.g., Machine Tool Emergency Stop, Single Deceleration)
During short-term braking, the resistor dissipates “pulse power,” so selection should be based on average power. The formula is:\( P_{b} = \frac{K \times P_{e} \times t_{b}}{t_{c} + t_{b}} \)
- \( K \): Regenerative power coefficient, related to the motor load type:
-
- Constant torque load (e.g., conveyor belts, mixers): \( K = 0.5 \sim 0.7 \);
-
- Variable torque load (e.g., fans, pumps): \( K = 0.3 \sim 0.5 \);
-
- Emergency stop or heavy-load lowering: \( K = 0.8 \sim 1.0 \);
- \( t_{b} \): Single braking time (s, e.g., 3s);
- \( t_{c} \): Braking interval (s, the time between two braking cycles, e.g., 30s);
- \( P_{e} \): Motor rated power (kW, e.g., 7.5kW).
Example: For a 7.5kW constant torque motor with a single braking time of 2s, a braking interval of 28s, and \( K=0.6 \):\( P_{b} = \frac{0.6 \times 7.5 \times 2}{28 + 2} = \frac{9}{30} = 0.3kW \)
→ A resistor with power ≥0.3kW can be selected (standard values such as 0.5kW or 1kW are used in practice to allow a margin).
(2) Continuous Braking Scenario (e.g., Frequent Braking of Elevators or Cranes)
During continuous braking, regenerative energy is generated continuously, so selection should be based on rated power. The formula is:\( P_{b} \geq K \times P_{e} \)
- At this time, \( K \) is 0.8~1.2 (long-term temperature rise must be considered for continuous braking), and \( P_{b} \leq P_{bmax} \) (the maximum allowable power of the inverter’s brake unit) must be satisfied.
Example: For an 11kW elevator motor with frequent up/down braking and \( K=1.0 \), \( P_{b} \geq 11kW \). If the maximum allowable power of the inverter’s brake unit is 15kW, an 11kW or 15kW resistor can be selected.
3. Verify the Resistor’s Rated Temperature Rise (Ensure Long-Term Stability)
The allowable temperature rise \( \Delta T \) of the resistor (℃, e.g., 150℃ for aluminum-housed resistors) must satisfy:\( \Delta T = \frac{P_{b} \times R_{th}}{S} \leq \Delta T_{max} \)
- \( R_{th} \): The thermal resistance of the resistor (℃/W, provided by the manufacturer, e.g., 0.5℃/W);
- \( S \): Heat dissipation coefficient (1 for natural cooling, 1.5~2 for forced air cooling);
- \( \Delta T_{max} \): The maximum allowable temperature rise of the resistor (℃, found in the product manual, e.g., 120℃).
If the calculated \( \Delta T \) exceeds \( \Delta T_{max} \), increase the resistor power or switch to forced air cooling.
IV. Summary of Selection Steps (4-Step Implementation Method)
Based on the above calculations, practical selection can be performed in 4 steps to ensure no omissions:
Step 1: Confirm Basic Parameters
Collect parameters such as motor rated power, inverter brake unit maximum current/power, braking time, and braking frequency. Clarify whether the braking type is short-term or continuous.
Step 2: Calculate the Minimum Resistance \( R_{bmin} \)
Calculate using \( R_{bmin} = U_{dc}/I_{bmax} \). The selected resistor value must be ≥\( R_{bmin} \), and a standard resistance value should be chosen (common standard values: 10Ω, 15Ω, 20Ω, 27Ω, 30Ω, 50Ω, 100Ω, etc.).
Step 3: Calculate the Required Resistor Power \( P_{b} \)
Select the corresponding formula based on the braking type (short-term/continuous) for calculation. The selected power must be ≥ the calculated value and not exceed the maximum allowable power \( P_{bmax} \) of the inverter’s brake unit. Reference standard power values: 0.5kW, 1kW, 2kW, 3kW, 5kW, 10kW, 15kW, etc.
Step 4: Confirm Additional Specifications
- Resistor type: Select the material based on the environment: aluminum-housed resistors (high temperature resistance, good heat dissipation, suitable for industrial scenarios), ceramic resistors (small size, suitable for space-constrained scenarios), or corrugated resistors (large heat dissipation area, suitable for high-power continuous braking);
- Temperature resistance grade: If the ambient temperature exceeds 40℃, a resistor with temperature resistance ≥200℃ is required;
- Installation size: Ensure sufficient installation space for the resistor, and avoid placing it too close to other components to prevent local overheating.
V. Common Selection Misconceptions and Precautions (Avoid Mistakes)
- Misconception 1: Focusing only on resistor power and ignoring resistance value
If the resistance value is too small (e.g., the calculated requirement is ≥25Ω, but 10Ω is selected), the braking current will exceed \( I_{bmax} \), burning the brake unit or resistor. The resistance value must first meet ≥\( R_{bmin} \), then match the power.
- Misconception 2: Selecting for short-term braking when continuous braking is needed
For scenarios such as frequent elevator braking, selecting a low-power resistor based on short-term braking (e.g., the calculated requirement is 11kW, but 5kW is selected) will cause the resistor to overheat and burn out. Selection must be based on the rated power for continuous braking.
- Misconception 3: Ignoring the matching between the brake unit and resistor
If the inverter has no built-in brake unit, an external brake unit must be selected. At this time, the maximum current of the brake unit must be ≥ the rated current of the resistor (\( I_{b} = U_{dc}/R_{b} \)) to avoid brake unit overload.
- Precaution: Allow a Margin
In industrial scenarios, it is recommended to allow a 10%~20% margin based on the calculated value:
-
- Resistance: e.g., the calculated requirement is 25.6Ω, select 30Ω (17% margin);
-
- Power: e.g., the calculated requirement is 0.3kW, select 0.5kW (67% margin) to handle sudden overloads.
- Precaution: Heat Dissipation Design
Brake resistors generate a large amount of heat during operation (e.g., a 10kW resistor generates 36,000kJ of heat per hour). Ensure good ventilation in the installation environment:
-
- Natural cooling: Maintain a distance of ≥10cm between the resistor and other components; avoid enclosed spaces;
-
- Forced air cooling: For power ≥5kW, a cooling fan is recommended, with an air speed ≥2m/s.
VI. Selection Example (Practical Application Scenario)
Scenario: A three-phase 380V, 5.5kW constant torque motor (e.g., a conveyor belt), an inverter with a built-in brake unit (\( I_{bmax}=15A \), \( P_{bmax}=10kW \)), a braking time of 2s, a braking interval of 30s, and an ambient temperature of 25℃.
Selection Process:
- Basic parameters: \( P_{e}=5.5kW \), \( U_{dc}=513V \), \( I_{bmax}=15A \), \( t_{b}=2s \), \( t_{c}=30s \), \( K=0.6 \) (constant torque).
- Calculate \( R_{bmin} \): \( R_{bmin}=513/15â34.2Ω \), select the standard value 36Ω.
- Calculate \( P_{b} \): \( P_{b}=(0.6Ã5.5Ã2)/(30+2)=6.6/32â0.206kW \), select the standard value 0.3kW (with a margin).
- Confirm additional specifications: Select an aluminum-housed resistor (150℃ temperature resistance) with natural cooling, and ensure the installation size matches the control cabinet space.
Final Selection Result: 36Ω/0.3kW aluminum-housed brake resistor.